1. Technical Specifications A9K24316
-
Operational Voltage (Ue): Up to 400/415 V AC (three-phase applications)
-
Number of Poles: 3 (suitable for full three-phase protection)
-
Rated Current (In): 16 Amperes
-
Tripping Curve: Type C – suitable for circuits with moderate inrush currents such as lighting, small motors, and HVAC systems
-
Breaking Capacity: 6000 A (as per IEC 60898-1)
-
Installation: Standard 35 mm DIN rail mounting
-
Degree of Protection: IP20 (or IP40 when placed in an appropriate enclosure)
-
Insulation Class: Class II (enhanced safety with double insulation)
-
Electrical Endurance: Up to 20,000 operations under load
-
Mechanical Endurance: Up to 20,000 manual cycles
-
Operating Temperature Range: -25°C to +70°C
-
Compliance Standards: IEC 60898-1
2. Key Features
-
Three-Pole Protection: Offers synchronized disconnection of all three phases, ensuring complete isolation of the load in case of a fault
-
C Curve Tripping: Balances sensitivity and robustness, ideal for typical mixed-use loads (e.g., lighting, sockets, motors)
-
Compact Modular Design: Space-saving and easily installed in modern distribution panels
-
High Fault Interruption Capability: Protects against short circuits and overloads up to 6000 A
-
Safe Operation: Finger-safe terminals and visible ON/OFF indicators for user safety and status visibility
-
Robust Construction: High mechanical and electrical endurance for long service life
-
DIN Rail Mounting: Quick and secure installation in standard enclosures
-
Eco-Design: RoHS-compliant and made from recyclable materials to support environmental responsibility
3. Typical Applications
The A9K24316 is ideal for medium-load, three-phase applications in residential, commercial, and light industrial environments:
-
Three-Phase Lighting Circuits: For warehouses, workshops, and industrial lighting systems
-
Small Motors and Machinery: Offers protection for compressors, conveyors, or small pumps
-
HVAC Systems: Suited for air handling units and three-phase fans
-
Control Panels: Used in industrial automation and motor control centers
-
Elevator Control Circuits: Suitable for moderate power loads in lift systems
-
Educational and Research Facilities: For lab equipment and three-phase benches
-
Retail and Commercial Units: General-purpose three-phase load protection